HSR-500 Hot Stick High Voltage Detector
Hot-Stick High-Voltage Detectors
Genuine HASEGAWA for Europe — Commercial invoice for every order · Shipping across Europe
HASEGAWA
Hot-stick voltage detectors for overhead lines, switchyards and substations: 11 options from 3 kV distribution level to 550 kV transmission, including AC/DC models.

11 products
HASEGAWA · HSR-500
Hot-Stick High-Voltage Detectors
HASEGAWA · HSR-90N
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-170
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-20N
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-250
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-30
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-30L
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-70
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-70L
Hot-Stick High-Voltage Detectors
HASEGAWA · HST-W80L
Hot-Stick High-Voltage Detectors
Hot-stick high-voltage detectors are models supplied as a detector head together with an insulating stick. On overhead lines, in switchyards and in substations, the absence of voltage is verified by touching the conductor from a safe distance. Maintenance crews of distribution and transmission system operators, industrial companies operating MV/HV installations and contractors are the users of this group.
Three criteria stand out in selection: the nominal voltage of the line, the reach required and the need for AC or DC. Where several models share the same range, the difference lies in the starting (threshold) voltage or the stick length.
| Model | Operating voltage | Typical use |
|---|---|---|
| HST-30 | AC 3 kV – 34.5 kV | Distribution lines up to 34.5 kV (e.g. 6 kV – 33 kV) |
| HST-30L | AC 3 kV – 34.5 kV | L series, starting voltage 500 V ± 100 V |
| HST-20N | AC / DC 3 kV – 25 kV | Sites with both AC and DC systems |
| HST-70 | AC 20 kV – 80.5 kV | 33 kV-class to 66 kV systems |
| HST-70L | AC 20 kV – 80.5 kV | L series, starting voltage 3000 V ± 600 V |
| HST-W80L | AC 20 kV – 80.5 kV | L series, starting voltage 5000 V ± 1000 V |
| HSR-90N | AC / DC 6 kV – 90 kV | Wide range, sealed sensor design |
| HST-170 | AC 60 kV – 195.5 kV | 110 kV – 150 kV substations; 3145 mm stick |
| HST-250 | AC 150 kV – 287.5 kV | Transmission above 150 kV (e.g. 220 kV); 5055 mm stick |
| HSR-500 | AC 250 kV – 550 kV | The highest transmission voltages |
| WM | AC 6.6 kV – 500 kV | Visual detection by a rotating vane |
The L-series models use the same battery type and weigh approximately 3 kg. The HST-70L and HST-W80L cover the same range; only their response thresholds differ. On sites with parallel live circuits, a higher threshold generally reduces the risk of misleading indications caused by induced voltage. Where the standard stick does not reach, the G, H and J versions of the HST-30 and the HST-170J can be ordered with longer sticks.
Hold the stick only by its handle (grip) area; never measure with a damp, dirty or cracked stick. Test the detector before every measurement. A "dead" indication is not a permit to work; work must not start until the line has been earthed with transmission line earthing equipment.
For a summary of all classes see voltage detectors; for model selection see How to Choose a Voltage Detector, and for maintenance see our article on periodic inspection.
The ranges of the two models overlap between 150 kV and 195.5 kV. For 150 kV-class systems (e.g. 150 kV or 154 kV) the primary choice is the HST-170; if a longer reach is needed, the HST-170J with a 5055 mm stick or the HST-250 can be considered.